Temperature Sensor — Metal Plating & Photographic Process Solutions
Named chemicals
What LibertyCES's vendor documentation shows
Plating Bath Temperature Control is the first-listed application on Signet's own 2350 page. The material argument is unusually clean: the PVDF body 'outlasts metal sensors in aggressive liquids and eliminates the need for costly custom thermowells' — the sensor body IS the corrosion barrier, so there is no metal thermowell for chromic acid to attack. Pair with the chart finding that 316SS rates only C on chromic acid at every concentration and the case for a non-metallic temperature sensor in a plating line makes itself.
Materials documented for this service
- PVDF one-piece body (replaces a metal thermowell entirely)
- Pt1000 platinum RTD element
- In-line mounting 100°C @ 7.5 bar / 108 psi; submersible mounting 85°C @ 7.5 bar — a real lower ceiling for submersible use
Products cited for this service
Sourced to
- data/vendor-sources/gf-signet-instrumentation-catalog.md
Every material and product claim on this page traces to the vendor documentation listed above. Chemical compatibility depends on exact concentration, temperature, and duty cycle — confirm current specifications with the manufacturer and request a spec review before final specification.